Installation and Connection
Self-Supervision Contact (SC)/Life-Contact and IRIG-B00X
Ensure the correct tightening torques.
Terminal
Electro-mechanical assignment
The
Self-Supervision Contact (SC relay)/Life-Contact
cannot be configured. The system contact is a changeover
contact that picks up when the device is free from internal faults. While the device is booting up, the
Self-
Supervision Contact (SC relay)/Life-Contact
remains dropped-off (unenergized). As soon as the system is properly
started (and protection is active), the
Self-Supervision Contact (SC relay)/Life-Contact
picks up and the assigned
LED (System OK) is activated accordingly (please refer to the Self Supervision chapter).
100 MCDGV4 DOK-HB-MCDGV4-2E