Switchgear/Breaker – Manager
Controlled Circuit Breaker
SG[1]
Direct Commands of a Controlled Circuit Breaker
Parameter Description Setting range Default Menu path
Manipulate
Position
WARNING! Fake Position - Manual Position
Manipulation
inactive,
Pos OFF,
Pos ON
inactive [Control
/SG
/SG[1]
/General
Settings]
Res SGwear Sl
SG
Resetting the slow Switchgear Alarm inactive,
active
inactive [Operation
/Reset]
Ack TripCmd Acknowledge Trip Command inactive,
active
inactive [Operation
/Acknowledge]
Global Protection Parameters of a Controlled Circuit Breaker
Parameter Description Setting range Default Menu path
Aux ON The CB is in ON-position if the state of the
assigned signal is true (52a).
1..n, DI-
LogicList
DI Slot X1.DI
1
[Control
/SG
/SG[1]
/Pos Indicatrs
Wirng]
Aux OFF The CB is in OFF-position if the state of the
assigned signal is true (52b).
1..n, DI-
LogicList
DI Slot X1.DI
2
[Control
/SG
/SG[1]
/Pos Indicatrs
Wirng]
Ready Circuit breaker is ready for operation if the
state of the assigned signal is true. This
digital input can be used by some protective
elements (if they are available within the
device) like Auto Reclosure (AR), e.g. as a
trigger signal.
1..n, DI-
LogicList
-.- [Control
/SG
/SG[1]
/Pos Indicatrs
Wirng]