EasyManua.ls Logo

Woodward HighPROTEC - EMC Immunity Tests

Woodward HighPROTEC
1369 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Standards
EMC Immunity Tests
Fast transient disturbance immunity test (Burst)
IEC 60255-22-4
IEC 61000-4-4
class 4
Power supply, mains inputs
Other in- and outputs
±4 kV, 2.5 kHz
±2 kV, 5 kHz
Surge immunity test (Surge)
IEC 60255-22-5
IEC 61000-4-5
class 4
Within one circuit
Circuit to earth
2 kV
4 kV
class 3 Communication cables to earth 2 kV
Electrical discharge immunity test (ESD)
IEC 60255-22-2
IEC 61000-4-2
class 3
Air discharge
Contact discharge
8 kV
6 kV
Radiated radio-frequency electromagnetic field immunity test
IEC 60255-22-3
IEC 61000-4-3
26 MHz – 80 MHz
80 MHz – 1 GHz
1 GHz – 3 GHz
10 V/m
35 V/m
10 V/m
Immunity to conducted disturbances induced by radio frequency fields
IEC 61000-4-6
class 3
150kHz - 80MHz 10 V
Power frequency magnetic field immunity test
IEC 61000-4-8
class 4
continues
3 sec
30 A/m
300 A/m
1233 MCDGV4 DOK-HB-MCDGV4-2E