Field Parameters
Field Parameters – Phase Differential Current
Parameter Description Setting range Default Menu path
Id Cutoff Level The Differential Current shown in the
Display or within the PC Software will be
displayed as zero, if the Differential Current
falls below this Cutoff Level. This parameter
has no impact on recorders.
0.0 - 0.100In 0.005In [Device Para
/Measurem
Display
/Diff]
IS Cutoff Level The Restraint Current shown in the Display
or within the PC Software will be displayed
as zero, if the Restraint Current falls below
this Cutoff Level. This parameter has no
impact on recorders.
0.0 - 0.100In 0.005In [Device Para
/Measurem
Display
/Diff]