Parameters
Setting Lock
By means of the
Setting Lock
, parameter settings can be locked against any changes as long as the assigned
signal is true (active). The
Setting Lock
can be activated within menu
[Field Para/General Settings/Lock Settings].
Bypass of the Setting Lock
The setting lock can be overwritten (temporarily) in case that the status of the signal that activates the setting lock
cannot be modified or should not be modified (spare key).
The
Setting Lock
can be bypassed by means of the Direct Control Parameter »
Setting Lock Bypass«
[Field Para/General Settings/Setting Lock Bypass]. The protective device will fall back into the
Setting Lock
either:
Directly after a parameter change has been saved, else
10 minutes after the bypass has been activated.
475 MCDGV4 DOK-HB-MCDGV4-2E