Statistics
Direct Commands
Parameter Description Setting range Default Menu path
ResFc all Resetting of all Statistic values (Current
Demand, Power Demand, Min, Max)
inactive,
active
inactive [Operation
/Reset]
ResFc Vavg Resetting of the sliding average calculation. inactive,
active
inactive [Operation
/Reset]
ResFc I
Demand
Resetting of Statistics - Current Demand
(avg, peak avg)
inactive,
active
inactive [Operation
/Reset]
ResFc P
Demand
Resetting of Statistics - Power Demand (avg,
peak avg)
inactive,
active
inactive [Operation
/Reset]
ResFc Min Resetting of all Minimum values inactive,
active
inactive [Operation
/Reset]
ResFc Max Resetting of all Maximum values inactive,
active
inactive [Operation
/Reset]
Global Protection Parameters of the Statistics Module
Parameter Description Setting range Default Menu path
ResFc Max Resetting of all Maximum values 1..n,
Assignment List
-.- [Device Para
/Statistics
/Min / Max]
ResFc Min Resetting of all Minimum values 1..n,
Assignment List
-.- [Device Para
/Statistics
/Min / Max]
Start Vavg via: Start sliding average supervision by: Duration,
StartFct
Duration [Device Para
/Statistics
/Vavg]
256 MCDGV4 DOK-HB-MCDGV4-2E