Yamatake Corporation Maintenance and Troubleshooting
ST3000 Smart Transmitter Series 900 Electronic Differential Pressure/Pressure Transmitter 7-5
7-1-5 :Zero Adjustment Using External Zero Adjustment Mechanism
(Option)
Setting the set range (LRV/URV) based on the current input value in "7-1-1 : Over-
view" applies to zero adjustment using an external zero adjustment mechanism. There-
fore, the LRV and the URV are automatically written by this operation. The factory set
zero point calibration data is not rewritten.
The adjusting procedure is found in "5-12 : External Zero and Span Adjustment
(Option)".
2
0mA
4mA
10kP
a