Yamatake Corporation Operation of the Transmitter
ST3000 Smart Transmitter Series 900 Electronic Differential Pressure/Pressure Transmitter 5-7
5-2-7 :Checking Damping Time Constant
Procedure
Check the damping time constant using the following procedure.
Here, it is assumed that [1.0 second] is set for the damping time constant.
To change the damping time constant, refer to "6-7-10 : Display or Change Damping
Time Constant".
5-2-8 :Checking Sealed Liquid Temperature Correction Function Set-
ting
Procedure
Check that the sealed liquid temperature correction function is set by the following
procedure.
This function is not set when the height display on the SFC screen is “0 m.”
For the procedure for changing the setting, refer to "6-7-15 : Displaying and changing
the sealed liquid temperature correction function".
Step Description SFC screen
1
Press the key.
Step Description SFC screen
1
Press the key.
2
Press the key. Or else, press
the key four times.
3
Press the key.
4
Press the key twice.
C
DAMP
DAMP FIT-1234
1.0 s
B
CONF
DSTJ CONFIG
CONFORM?
H
NEXT
L
PREV
DSTJ CONFIG
SAVE/RESTORE?
ENTER
( Yes )
NON-VOL
SAVE DATA
WORKING...
CLR
( No )
DSTJ FIT-1234
READY...