Yamatake Corporation Maintenance and Troubleshooting
ST3000 Smart Transmitter Series 900 Electronic Differential Pressure/Pressure Transmitter 7-27
8
Press the keys.
9
Press the keys.
• The low limit value is calibrated.
10
Press the and keys, in that order
• Data is forcefully saved.
11 Turn OFF the transmitter. Waiting for at
least 2 seconds. Turn on transmitter again.
12
Press the keys.
13
Press the keys.
The # mark disappears.
Step Description SFC screen
ENTER
( Yes )
NON-VOL
LRV FIT-1234
ARE YOU SURE?
ENTER
( Yes )
NON-VOL
LRV FIT-1234
WORKING...
LRV FIT-1234
LRV CORRECTED #
SHIFT
ENTER
( Yes )
NON-VOL
SHIFT- #
DSTJ FIT-1234
WORKING...
DSTJ FIT-1234
DATA NONVOLATILE#
A
ID
DE READ
TAG No.
WORKING...
DSTJ TAG NO.
LIN DP FIT-1234
U
STAT
F/S DIR
DSTJ FIT-1234
WORKING...
DSTJ FIT-1234
STATUS CHECK=OK