Yamatake Corporation Maintenance and Troubleshooting
ST3000 Smart Transmitter Series 900 Electronic Differential Pressure/Pressure Transmitter 7-33
An operation error is suspect.
Message Meaning Required action
Wrong key input
Wrong key input
procedure
Press the g key to check the
display and start the key input
again.
Calibration required Calibrate the low and high
limit values of the set range.
Key unsupported Press correct key
Excessive span cali-
bration
Check that the input pressure
agrees with the calibrated
value and calibrate the high
limit of the set range.
Requested output
value > Output range
(-1.25%~105%) in
constant current
source mode
Press the g key and input data
again.
Excessive zero cali-
bration
Check that the input pressure
agrees with the calibrated
value and calibrate the low
limit of the set range.
The transmitter data-
base is not correct
when the SFC is
turned ON.
Start the communications
again.
Check the database, cali-
brate the transmitter again,
and in put correct data.
Appropriate input
value for the setting?
Check the input value.
If it is wrong, correct it.
Set range > High
limit of set range x
1.5
Press the key to check the
numeric value, and repeat the
setting procedure.
Invalid request Check SFC operation proce-
dure.
KEY NOT ALLOWD!
CORRECT RESET #
NOT SUPPORT
EXCESS SPAN CORR
#
EXCESSIVE OUTPUT
EXCESS ZERO CORR
#
INVALID DATABASE
CORRECT LRV?
ENTRY > SEN RANGE
INVALID REQUEST