n
Related Parameters
No. Parameter Name Setting Values
A1-01 Access Level Selection
Default: 2
Range: 0 to 3
A1-03 Initialize Parameters
Default: 0
Range: 0 to 5550; 6008 to 6014; 7770, 7771
E2-01 Motor Rated Current
Default:
Min.: 10% of drive rated current
Max.: 200% of drive rated current
E2-04 Number of Motor Poles
Default: 2
Min.: 2
Max.: 48
P1-03 Feedback Device Scaling
Default: 145.0 PSI
Min.: 0.1
Max.: 6000.0
P1-11 High Feedback Level
Default: 0.0 PSI
Min.: 0.0
Max.: 6000.0
P1-06 Minimum Pump Speed
Default: 40.0 Hz
Min.: 0.0
Max.: [E1-04]
P1-04 Start / Draw Down Level
Default: 0.0
Min.: -999.9
Max.: 999.9
P2-02 Sleep Level
Default: 0.0 Hz
Min.: 0.0
Max.: 6000.0
P4-10 AUTO Mode Operator Run Power Down Storage
Default: 0
Range: 0, 1
P5-02 HAND Speed Reference 1
Default: 40.0 Hz
Min.: 0
Max.: [E1-04]
P5-04 HAND Key Function Selection
Default: 1
Range: 0, 1
Q1-01 PID Controller Setpoint 1
Default: 0.0
Min.: 0.0
Max.: 6000.0
U1-99 Anti-No-Flow Timer No signal output available
4.6 iQpump Presets and Functions
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
151
4
Start-Up Programming
& Operation