LCD Display Description
Delta Volume: Full display with units, commas, and sign.
Delta Volume: Full display with no units, no commas, and
resolution decreased.
n
Low Flow Detection Delay at Start Cancel
The Low Flow Rate detection is enabled when all of the following are true:
• There is a valid flow meter input: pulse input, analog input, or MEMOBUS network.
• The Low Flow Level parameter P6-06 > 0.
• The drive is running in Hand or Auto and the output frequency is greater than 0 for longer than the time set in P6-08.
n
Related Parameters, Monitors, and Multi-Function Digital Output Settings
No. Parameter Name Setting Values
P6-01 Flow Meter Scaling
Default: 0.0 GPM
Range: 0.0 to 6000.0 GPM
P6-02 Turbine Input Scaling (Coarse)
Default: 0 ppG
Range: 0 to 6000 ppG
P6-03 Turbine Input Scaling (Fine)
Default: 0.0000 ppG
Range: 0.0000 to 0.9999 ppG
P6-06 Low Flow Level
Default: 0.0
Range: 0.0 to 6000.0
P6-07 Low Flow Detection Delay Time When Already Running
Default: 10 s
Range: 0 to 6000 s
P6-08 Low Flow Detection Wait Time At Start
Default: 0.0 min
Range: 0.0 to 3600.0 min
P6-09 Low Flow Select
Default: 1
Range: 0 to 3
P6-17 High Flow Level
Default: 0.0
Range: 0.0 to 6000.0
4.6 iQpump Presets and Functions