No. Parameter Name Setting Values
P6-21 Low Flow Detection Delay @ Start Cancel Time
Default: 5 s
Range: 0 to 6000 s
P6-22 Flow Meter Decimal Place Position
Default: 1
Range: 0 to 2
P6-26 Flow Limit Selection
Default: 0
Range: 0 to 2
P6-27 Flow Limit Level
Default: 0.0
Range: 0.0 to 6000.0
P6-28 Flow Limit Regulator Gain
Default: 0.00
Range: 0.00 to 25.00
P6-29 Flow Limit Regulator Integral Time
Default: 1.00 s
Range: 0.00 to 25.00 s
P6-30 Flow Limit Regulator Delay @ Start
Default: 10 s
Range: 0 to 6000 s
P6-35 Accumulator Delta Save Selection
Default: 0
Range: 0 to 2
P6-36 Delta Starting Accumulation Level - Millions
Default: 0
Range: 0 to 65535
P6-37 Delta Starting Accumulation Level - Thousands
Default: 0
Range: 0 to 999
P6-38 Delta Starting Accumulation Level - Ones
Default: 0
Range: 0 to 999
P6-39 Delta Starting Accumulation Level - Decimal
Default: 0.0000
Range: 0.0000 to 0.9999
P9-41 Add Flow Level
Default: 0.0 GPM
Range: 0.0 to 6000.0 GPM
P9-42 Remove Flow Level
Default: 0.0 GPM
Range: 0.0 to 6000.0 GPM
U1-83 Flow Rate Full scale: P6-01 Setting
U1-88 Total Volume Accumulated Full scale: N/A
U1-89 Delta Volume Accumulated Full scale: N/A
H2 Multi-Function Digital Output Settings
H2-oo
Function Description
A7 Flow Rate Limit Closed: The Flow Rate is actively affecting the output speed.
4.6 iQpump Presets and Functions
202
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual