HOA Keypad Display Error Name
oPE33 Parameter selection is incompatible with the selected network P9-99
Cause Possible Solutions
When P1-01 = 3 (MEMOBUS Networking) and
P9-99 = 0 (A-Version 30034), one of the following
parameters has been set:
P9-01 = 2 (Stop History)
P9-05 = 3 (Follow Lead Speed)
Q4-01 > 0 (Water Level Enabled)
Q5-01 > 0 (Suction Pressure Control Enabled)
P6-01 > 0 (Flow Meter Enabled) and P9-40 = 3
(Network)
Confirm parameter settings for P1-01, P9-99, P6-01, P9-05, P9-40, Q4-01, and Q5-01.
HOA Keypad Display Minor Fault Name
oPE34
DeScale Set Err
De-Scale Setting Error
Cause Possible Solution
The De-scale function is not allowed while Anti-
Jam or MEMOBUS Multiplex is enabled.
Review settings of parameters P1-01, P7-01, or P8-01.