Digital Operator Display Error Name
oPE18
Online Tuning Parameter Setting Error
Parameters controlling online tuning are not set correctly.
Cause Possible Solutions
One of the following errors occurred while online
tuning was enabled in OLV (A1-02 = 2):
• E2-02 was set below 30% of the original default
value
• E2-06 was set below 50% of the original default
value
• E2-03 = 0
Set E2-02, E2-03, and E2-06 to the correct values.
HOA Keypad Display Error Name
oPE28
<1>
Sequence Timer Error
One or more of the sequence timers is not set in the correct order.
Cause Possible Solutions
One of the following contradictory settings is true:
• S2-01 > S2-02
• S2-06 > S2-07
• S2-11 > S2-12
• S2-16 > S2-17
Correct the parameter settings.
<1> Available in drive software versions PRG: 8551 and earlier.
HOA Keypad Display Error Name
oPE29 Geothermal Set Error
Cause Possible Solutions
P1-01 parameter selection is not compatible with
Geothermal Mode (b1-01 = 5).
Confirm b1-01 and P1-01 parameter settings.
HOA Keypad Display Error Name
oPE30 Flow Meter Input Error
Cause Possible Solutions
Analog and pulse flow meters are programmed
simultaneously.
H6-01 is set to 5 and either H3-02, H3-06, or H3-10
is set to 22.
Reprogram H6-01, H3-02, H3-06, or H3-10.
Flow meter scaling is set to 0 and the flow meter
is being used as PID feedback.
P6-01 is set to 0.0, P1-02 is set to 25 and b5-01 is
set to a value higher than 0.
Reprogram P6-01, P1-02, or b5-01.
HOA Keypad Display Error Name
oPE31 Water Level/Suction Pressure/PI Aux
Cause Possible Solutions
One or both of the following conditions are
present:
• More than one of these parameters is set to a non-
zero value: Q4-01, Q5-01, or Q6-01.
•
Both Water Level/Suction Pressure (H3-oo =
23) and PI Aux FB Level (H3-oo = 27) are
programmed.
Confirm parameter settings of Q4-01, Q5-01, Q6-01, H3-02, H3-06 and H3-10.
HOA Keypad Display Error Name
oPE32 Incompatible Network Water Level/Suction Pressure Mode
Cause Possible Solutions
Low Water Level or Suction Pressure Turn-Off
Method (P9-51) is restricted to Water Level Source
of Analog Only (P9-50 = 0).
Confirm parameter settings for P9-50 and P9-51.
5.4 Operator Programming Errors
288