No.
(Addr.
Hex)
Name LCD Display Description Values Page
H1-28
(02DE)
External Fault 8 Delay
Time
EF8 Delay Time
Sets the amount of time delay applied to the EF8 fault.
(20 H1-08 2F)
Default: 0.00 s
Min.: 0.00
Max.: 300.00
H1-31
(09E1)
<2>
Terminal S1 On-Delay
Time
Term S1 On-Delay
Sets the length of time that Terminal S1 must be closed before
the drive performs the programmed function.
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
<3>
H1-32
(09E2)
<2>
Terminal S2 On-Delay
Time
Term S2 On-Delay
Sets the length of time that Terminal S2 must be closed before
the drive performs the programmed function.
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
<3>
H1-33
(09E3)
<2>
Terminal S3 On-Delay
Time
Term S3 On-Delay
Sets the length of time that Terminal S3 must be closed before
the drive performs the programmed function.
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
<3>
H1-34
(09E4)
<2>
Terminal S4 On-Delay
Time
Term S4 On-Delay
Sets the length of time that Terminal S4 must be closed before
the drive performs the programmed function.
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
<3>
H1-35
(09E5)
<2>
Terminal S5 On-Delay
Time
Term S5 On-Delay
Sets the length of time that Terminal S5 must be closed before
the drive performs the programmed function.
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
<3>
H1-36
(09E6)
<2>
Terminal S6 On-Delay
Time
Term S6 On-Delay
Sets the length of time that Terminal S6 must be closed before
the drive performs the programmed function.
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
<3>
H1-37
(09E7)
<2>
Terminal S7 On-Delay
Time
Term S7 On-Delay
Sets the length of time that Terminal S7 must be closed before
the drive performs the programmed function.
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
<3>
H1-38
(09E8)
<2>
Terminal S8 On-Delay
Time
Term S8 On-Delay
Sets the length of time that Terminal S8 must be closed before
the drive performs the programmed function.
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
<3>
H1-41
(09EB)
<2>
Terminal S1 Off-Delay
Time
Term S1 OffDelay
Sets the length of time needed for Terminal S1 to be open before
the drive removes the programmed function.
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
<3>
H1-42
(09EC)
<2>
Terminal S2 Off-Delay
Time
Term S2 OffDelay
Sets the length of time needed for Terminal S2 to be open before
the drive removes the programmed function.
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
<3>
H1-43
(09ED)
<2>
Terminal S3 Off-Delay
Time
Term S3 OffDelay
Sets the length of time needed for Terminal S3 to be open before
the drive removes the programmed function.
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
<3>
H1-44
(09EE)
<2>
Terminal S4 Off-Delay
Time
Term S4 OffDelay
Sets the length of time needed for Terminal S4 to be open before
the drive removes the programmed function.
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
<3>
H1-45
(09EF)
<2>
Terminal S5 Off-Delay
Time
Term S5 OffDelay
Sets the length of time needed for Terminal S5 to be open before
the drive removes the programmed function.
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
<3>