No.
(Addr.
Hex)
Name LCD Display Description Values Page
H1-46
(09F0)
<2>
Terminal S6 Off-Delay
Time
Term S6 OffDelay
Sets the length of time needed for Terminal S6 to be open before
the drive removes the programmed function.
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
<3>
–
H1-47
(09F1)
<2>
Terminal S7 Off-Delay
Time
Term S7 OffDelay
Sets the length of time needed for Terminal S7 to be open before
the drive removes the programmed function.
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
<3>
–
H1-48
(09F2)
<2>
Terminal S8 Off-Delay
Time
Term S8 OffDelay
Sets the length of time needed for Terminal S8 to be open before
the drive removes the programmed function.
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
<3>
–
<1> Value in parenthesis is the default setting when a 3-Wire initialization is performed (A1-03 = 3330).
<2> Available in drive software versions PRG: 8552 and later. Not available in drive models 4A0930 and 4A1200.
<3> Default is 0.00 s and range is 0.00 to 300.00 in drive software versions PRG: 8553 and earlier.
H1 Multi-Function Digital Input Selections
H1-oo
Setting
Function LCD Display Description Page
0 3-Wire sequence 3-Wire Control
Closed: Reverse rotation (only if the drive is set up for 3-Wire sequence)
Terminals S1 and S2 are automatically set up for the Run command and Stop
command.
–
2
External Reference 1/2
Selection
External Ref 1/2 Sel
Open: Run command and frequency reference source 1 (determined by b1-01 and
b1-02)
Closed: Run command and frequency reference source 2 (determined by b1-15
and b1-16)
–
3
Multi-Step Speed
Reference 1
Multi-Step Ref 1
When input terminals are set to Multi-Step Speed References 1 through 3,
switching combinations of those terminals will create a multi-step speed sequence
using the frequency references set in d1-01 through d1-08.
–
4
Multi-Step Speed
Reference 2
Multi-Step Ref 2
When input terminals are set to Multi-Step Speed References 1 through 3,
switching combinations of those terminals will create a multi-step speed sequence
using the frequency references set in d1-01 through d1-08.
–
5
Multi-Step Speed
Reference 3
Multi-Step Ref 3
When input terminals are set to Multi-Step Speed References 1 through 3,
switching combinations of those terminals will create a multi-step speed sequence
using the frequency references set in d1-01 through d1-08.
–
6 Jog reference selection jog Freq Ref
Closed: Jog frequency reference (d1-17) selected. Jog has priority over all other
reference sources.
–
7
Accel/decel time
selection 1
Multi-Acc/Dec 1
Used to switch between accel/decel time 1 (set in C1-01, C1-02) and accel/decel
time 2
(set in C1-03, C1-04).
–
8
Baseblock command
(N.O.)
Ext BaseBlk N.O. Closed: No drive output –
9
Baseblock command
(N.C.)
Ext BaseBlk N.C. Open: No drive output –
A Accel/decel ramp hold Acc/Dec RampHold
Open: Accel/decel is not held
Closed: The drive pauses during acceleration or deceleration and maintains the
output frequency.
–
B
Drive overheat alarm
(oH2)
OH2 Alarm Signal Closed: Closes when an oH2 alarm occurs –
C
Analog terminal input
selection
Term A2 Enable
Open: Function assigned by H3-14 is disabled.
Closed: Function assigned by H3-14 is enabled.
–
F Through mode Term Not Used
Select this setting when using the terminal in a pass-through mode. The terminal
does not trigger a drive function but can be used as digital input for the controller
the drive is connected to.
–
10 Up command Up Command 1
The drive accelerates when the Up command terminal closes, and decelerates when
the Down command closes. When both terminals are closed or both are open, the
drive holds the frequency reference. The Up and Down commands must always
be used in conjunction with one another.
–
B.8 H Parameters: Multi-Function Terminals
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
375
B
Parameter List