No.
Reference Pulse Form
Reference
Section
0 Sign + Pulse train, positive logic
5.4.1
1 CW + CCW pulse train, positive logic
2
Two-phase pulse train with 90
°
phase differential (phase A + phase B)
×
1, positive logic
3
Two-phase pulse train with 90
°
phase differential (phase A + phase B)
×
2, positive logic
4
Two-phase pulse train with 90
°
phase differential (phase A + phase B)
×
4, positive logic
5 Sign + Pulse train, negative logic
6 CW + CCW pulse train, negative logic
Clear Signal Form
Reference
Section
0 Clears position error when the signal is at high level.
5.4.2
1 Clears position error at the rising edge of the signal.
2 Clears position error when the signal is at low level.
3 Clears position error at the falling edge of the signal.
Clear Operation
Reference
Section
0 Clears position error at the baseblock (servomotor power OFF or alarm occurred).
5.4.2
1
Does not clear position error (possible to clear error counter only with CLR signal).
2
Clears position error when an alarm occurs.
Filter Selection
Reference
Section
0
Uses reference input filter 1 for line driver signal (to 1 Mpps).
5.4.1
1
Uses reference input filter for open collector signal (to 200 kpps).
2
Uses reference input filter 2 for line driver signal (1 Mpps to 4 Mpps).
4th 3rd 2nd 1st
digit digit digit digit
n.