3.1 Main Circuit Wiring
3-13
3
Wiring and Connection
(5) Power Supply Capacities and Power Losses
The following table shows SERVOPACK’s power supply capacities and power losses when using single-
phase 200 V power supply.
The official model number is SGDV-120A11A008000.
Note 1. SGDV-R70A, -R90A, -1R6A, and -2R8A SERVOPACKs do not have built-in regenerative resistors. If the regen-
erative energy exceeds the specified value, connect an external regenerative resistor between B1/ and B2.
2. Regenerative resistor power losses are allowable losses. Take the following action if this value is exceeded.
Remove the lead or shorting bar between terminals B2 and B3 on the SERVOPACK main circuit of SGDV-
5R5A, -120A SERVOPACKs.
Install an external regenerative resistor between external regenerative resistor connection terminals B1/ and
B2.
3. External regenerative resistors are not included.
(6) How to Select Molded-case Circuit Breaker and Fuse Capacities
The following table shows the SERVOPACK’s current capacities and inrush current when using single-phase
Use these values as a basis for selecting the molded-case circuit breaker and fuse.
The official model number is SGDV-120A11A008000.
Note 1. To comply with the EU low voltage directive, connect a fuse to the input side as protection against accidents
caused by short-circuits. Select the fuse for the input side that are compliant with UL standards.
The table above also provides the net values of current capacity and inrush current. Select a fuse and a molded-
case circuit breaker which meet the breaking characteristics shown below.
Main circuit, control circuit: No breaking at three times the current values shown in the table for 5 s.
Inrush current: No breaking at the current values shown in the table for 20 ms.
2. The following restrictions apply to UL standard compliance conditions for SGDV-120A11A008000 SERVO-
PACKs.
Current rating when using molded-case circuit breaker: 40 A max.
Main Circuit
Power
Supply
Maximum
Applicable
Servomotor
Capacity
[kW]
SERVOPACK
Model SGDV-
Power Supply
Capacity per
SERVOPACK
[kVA]
Output
Current
[Arms]
Main
Circuit
Power
Loss
[W]
Regenerative
Resistor
Power Loss
[W]
Control
Circuit
Power
Loss
[W]
To ta l
Power
Loss
[W]
Single-phase,
200 V
0.05 R70A 0.2 0.66 5.2
17
22.2
0.1 R90A 0.3 0.91 7.4 24.4
0.2 1R6A 0.7 1.6 13.7 30.7
0.4 2R8A 1.2 2.8 24.9 41.9
0.75 5R5A 1.9 5.5 52.7 8 77.7
1.5
120A
*
4 11.6 68.2 10 22 100.2
Main Circuit
Power
Supply
Maximum
Applicable
Servomotor
Capacity
[kW]
SERVOPACK
Model
SGDV-
Power Supply
Capacity per
SERVOPACK
[kVA]
Current Capacity Inrush Current
Main
Circuit
[Arms]
Control
Circuit
[Arms]
Main
Circuit
[A0-p]
Control
Circuit
[A0-p]
Single-
phase,
200 V
0.05 R70A 0.2 2
0.2
33
70
0.1 R90A 0.3 2
0.2 1R6A 0.7 3
0.4 2R8A 1.2 5
0.75 5R5A 1.9 9
33
1.5
120A
*
4160.25