5-28
Related Parameters
Adjusting Torque Compensation Gain (C4-01)
Normally, there is no need to change this setting. If adjustments are necessary do the following:
Open Loop Vector control
If the torque response is slow increase the setting value.
If vibrations occur decrease the setting value.
V/f control
If the cable is very long, increase the set value.
If the motor capacity is smaller than the Inverter capacity (max. applicable motor capacity), increase the
set value.
If the motor is vibrating, reduce the set value.
Setting precautions
Adjust this parameter so that the output current during low-speed rotation does not exceed the Inverter
rated output current range.
Adjust the value in steps of 0.05 only.
Adjusting the Torque Compensation Delay Time Constant (C4-02)
The factory setting depends on the control mode. The factory settings are:
V/f control: 200 ms
Open loop vector control: 20 ms
Normally, there is no need to change this setting. If adjustments are necessary do the following:
If the motor is vibrating or if overshooting occurs, increase the set value.
If the torque response is slow, decrease the set value.
Parameter
No.
Name
Factory
Setting
Change
during
Operation
Control Methods
V/f
Open
Loop
Vector
Closed
Loop
Vector
C4-01 Torque compensation gain 1.00 Yes A A No
C4-02 Torque compensation delay time constant 2000 ms No A A No
C4-03 Starting torque compensation value (forward direction) 0.0 No No A No
C4-04 Starting torque compensation value (reverse direction) 0.0 No No A No
C4-05 Starting torque compensation time constant 1 ms No No A No