4-8
User Parameter Tables
A: Setup Settings
Initialize Mode: A1
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Register
Page
V/f
Open
Loop
Vector
Closed
Loop
Vector
Display
A1-00
Language
selection for
Digital Oper-
ator/Monitor
display
Used to select the language
displayed on the Digital Oper-
ator/Monitor (JVOP-160 only).
0: English
1: Japanese
2: German
3: French
4: Italian
5: Spanish
6: Portuguese
This parameter is not changed
by the initialize operation.
0 to 6 0 Yes A A A 100H –
Select
Language
A1-01
Parameter
access level
Used to set the parameter
access level (set/read.)
0: Monitoring only
(Monitoring drive mode
and setting A1-01 and A1-
04.)
1: Used to select user
parameters (Only
parameters set in A2-01 to
A2-32 can be read and set.)
2: Advanced
(Parameters can be read
and set in both, quick
programming mode (Q)
and advanced
programming mode (A).)
0 to 2 2 Yes Q Q Q 101H 5-60
Access Level
A1-02
Control
method
selection
Used to select the control
method for the Inverter
0: V/f control
2: Open loop vector
3: Closed Loop Vector
This parameter is not changed
by the initialize operation.
0 to 3 3 No Q Q Q 102H –
Control
Method
A1-03
Initialize
Used to initialize the parame-
ters using the specified
method.
0: No initializing
1110: Initializes using the
user parameters
2220: Initializes using a
two-wire sequence.
(Initializes to the
factory setting.)
0 to
2220
0 No A A A 103H –
Init Parame-
ters
A1-04
Password
Password input when a pass-
word has been set in A1-05.
This function write-protects
some parameters of the initial-
ize mode.
If the password is changed,
A1-01 to A1-03 and A2-01 to
A2-32 parameters can no
longer be changed. (Program-
ming mode parameters can be
changed.)
0 to
9999
0 No A A A 104H 5-60
Enter Pass-
word