* 1. The setting range is 10% to 200% of the Inverter's rated output current. The value for a 200 V class inverter of 3.7 kW is given.
* 2. The factory setting depends upon the Inverter capacity. The value for a 200 V class inverter of 3.7 kW is given.
* 3. The setting range depends on the inverter capacity. The value for a 200 V class inverter of 3.7 kW is given.
E2-10
Motor iron
loss for
torque com-
pensation
Sets motor iron losses.
0 to
65535
112 W
*2
No A No No 317H 5-50
Tcomp Iron
Loss
E2-11
Motor rated
output power
Sets the rated output power of
the motor.
This parameter is an input data
for autotuning.
0.00 to
650.00
3.70
*2
No Q Q Q 318H 5-50
Mtr Rated
Power
E2-12
Motor iron
saturation
coefficient 3
This parameter is automati-
cally set during rotating auto-
tuning.
1.30 to
1.60
1.30 No No A A
Saturation
Comp 3
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Register
Page
V/f
Open
Loop
Vector
Closed
Loop
Vector
Display
http://nicontrols.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed L7 and is the answer not in the manual?

YASKAWA Varispeed L7 Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed L7
CategoryInverter
LanguageEnglish

Related product manuals