1-36
Report Data (/M1, /PM1 Option)
The average or instantaneous value, and maximum, minimum, and sum can be
computed for the specified channels at the preset interval, and the result can be
acquired to the internal memory.
Reports are created from the time the data acquisition is started till the data
acquisition is stopped.
Reports are created at each time interval (one hour for hourly report, one day for
daily report, etc) and when the data acquisition is stopped.
You can select report type from hourly, daily, hourly and daily, daily and weekly, or
daily and monthly.
Time
Start
writing data to
internal memory
T1
Stop writing data
T2
t1 t2 tn
tn+1
The average (or instantaneous data), maximum, minimum, and sum for the
specified channels stored to the internal memory.
The interval time for the report creation (1 hour, 1 day, 1week, or 1 month)
Up to 40 data sets can be stored in the internal memory. When this number is
exceeded, data are overwritten from the oldest data.
For “hourly only”, this constitutes 40 minutes of report data. For “daily+monthly”,
this constitutes 39 daily reports and one monthly report or 38 daily reports and two
monthly reports.
Note
The number of report data sets in the internal memory can be confirmed with the memory
summary. See section 1.4 .
1.5 Data Storage Function

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA FX103 and is the answer not in the manual?

YOKOGAWA FX103 Specifications

General IconGeneral
BrandYOKOGAWA
ModelFX103
CategoryController
LanguageEnglish

Related product manuals