Section 5 Run-Time Operation Re-import
9ARD000014-600 A 169
2. If in the next re-import if the de-selected modules from point 1 above are
selected again and the import is proceeded, the hardware types for the newly
selected I/O modules are created with new hardware ID's. If such I/O module
were already available under adapter in the hardware tree, they to be deleted
and has to be added again under the adapter.
When re-importing an EDS file, the name and location of the EDS file should be
same as the previously imported EDS files. If these are the same, then the Device
Import Wizard considers this as a re-import. Else the Device Import Wizard
considers this as a fresh import.
Hence, re-importing of an EDS file is not possible if the EDS file is renamed and
then re-imported.
The user can choose for fresh import instead of a re-import, if the newly created
hardware type has to coexist with old hardware type.
In case the configuration imported for EDS file is not correct, the hardware type
should not be deleted from the hardware library, after it has been created by
importing an EDS file in Control Builder.
Instead, to correct the configuration, re-import the EDS file in the same hardware
library, or create a new hardware library and import the EDS file under it.