Section 7 Technical Data
General Technical Data
The general technical data that need to be considered while Connecting to the
DeviceNet and EtherNet/IP devices are:
CI873 communicates only on Auto negotiation. Due to this it is recommended
and mandatory to configure the switch port to which CI873 is connected as
Auto negotiation.
For the CI873 to connect to the DeviceNet devices and EtherNet/IP devices, the
EDS file of the devices should have all the mandatory connection information
as mentioned in
Section , Device Import Wizard.
Tag based Class 1 connection information should be available in the EDS file
of the Logix 5000 Controllers for communication with the CI873 as mentioned
in
Section , Device Import Wizard.
The number of I/O modules that can be connected under EtherNet/IP or
DeviceNet device adapter type device is 63.
The number of configuration parameters supported per EtherNet/IP or
DeviceNet device is 1000.
The CI873 supports listen only connection with the EtherNet/IP device,
provided that there is already exclusive owner connection in the device.
The CI873 does not support redundant owner connections for the EtherNet/IP
devices. That is, at the same time both primary and backup CI873 cannot
connect to the same assembly object of the EtherNet/IP device even though the
device supports such connections.
Read Only and Monitoring Parameters in EDS file of the
EtherNet/IP/DeviceNet device are not supported. That is, DIW ignores such
parameters while generating the Hardware type from the EDS file.