9ARD000014-600 A 223
Appendix A Troubleshooting EDS File
Table 41 shows the messages that are displayed during the import of EDS files using
the Device Import Wizard:
Table 41. Messages - Import of EDS Files
Sl
No
Message Reason
Applicability
Based on Device
Classification
Additional
Information and
Workaround
1 There are important
changes in some
basic device
information between
the current EDS
file. Major
revision has been
changed (1-->2).
Please cancel the
process and use a
different new
Library to import
the revised version
of EDS.
During a re-import,
the major revision of
the EDS file is
different from the
EDS file used in first
import.
EtherNet/IP/
DeviceNet
Import will abort.
Start a fresh import of
the EDS file in a new
hardware library.
2 The EDS file used
to invoke the
wizard is a modular
IO. Please invoke
the wizard with an
adapter EDS file
and proceed with
the import process
The file used to
invoke the wizard is
an IO file and not an
adapter.
Modular
EtherNet/IP/
DeviceNet
Import will abort.
Start the import with
adapter EDS file, and
not with IO EDS file.