Appendix A Troubleshooting EDS File
224 9ARD000014-600 A
3 There is more than
one adapter
selected. Please
select one and only
one adapter with
the IO modules and
proceed with the
import process
There are more
than one adapter
selected by the user
which is not
allowed.
Modular
EtherNet/IP/
DeviceNet
Deselect one adapter
to proceed with the
import.
4 An adapter of the
similar name from a
folder other than
the current folder
has been imported.
Please select the
adapter from the
earlier folder or
change the name of
the adapter EDS
being imported and
try again
Adapter file from a
different folder with
the same name is
not allowed. This is
observed during a
re-import.
Modular
EtherNet/IP/
DeviceNet
Import will abort.
During re-import,
select the adapter file
from the folder that
was from the same
location as selected
during fresh import.
5 Please cancel the
process and use a
different/new
Library to import
the revised version
of EDS file.
Major revision has
been changed in
re-import which is
not allowed.
EtherNet/IP/
DeviceNet
Import will abort.
Start a fresh import of
the EDS file in a new
hardware library.
Table 41. Messages - Import of EDS Files (Continued)
Sl
No
Message Reason
Applicability
Based on Device
Classification
Additional
Information and
Workaround