LD 800DN System Files Section 6 Linking Device LD 800DN
206 9ARD000014-600 A
ip_accs.cfg — It is possible to configure which IP addresses and what protocols are
allowed for connecting to the module. This information is stored in the ip_accs.cfg
file.
The file contains one or several of these headers:
•[Web]
[FTP]
•[Ethernet/IP]
[All]
Under each header the allowed IP addresses are written. The wildcard '*' can be
used to allow series of IP addresses. If a protocol header is not given, then the
system uses the configuration set under the [All] header. If the [All] header is not
given, then the protocol does not accept any connections.
Example for ip_accs.cfg is shown in Table 35.
[DHCP/BOOTP]
OFF
DHCP/BootP Enabled — ON
DHCP/BootP Disabled — OFF
In this case it is set as ‘OFF’
[Speed]
Auto
Auto — Autonegotiation is used
100 — Sets the module speed at
100mbits
10 — Sets the module speed at 10mbits
In this case, Autonegotiation is used
[Duplex]
Auto
Auto — Autonegotiation is used
Full — Sets the module to operate at full
duplex mode
Half — Sets the module to operate at
half duplex.
In this case, Autonegotiation is used