Appendix A Troubleshooting EDS File
246 9ARD000014-600 A
104 Member name already
exists!
No duplicate
member names
allowed.
EtherNet/IP Continue the import
with this message
after specifying
proper member name.
105 Invalid datatype If the datatype
doesn't match with
the list of datatypes
provided.
EtherNet/IP Continue the import
with this message
after specifying
proper datatypes.
106 Structure size
exceeds 500 bytes
If the structure size
exceeds 500 bytes.
EtherNet/IP Continue the import
with this message
after specifying
proper structure size.
107 Atleast one Class 1
or Class 3 channel
is required to
proceed further
with the import
User has not
configured any
Class 1 or Class 3
channels.
EtherNet/IP Import shall not
continue until user
creates Class 1 or
Class 3 channels.
Table 41. Messages - Import of EDS Files (Continued)
Sl
No
Message Reason
Applicability
Based on Device
Classification
Additional
Information and
Workaround