R8
2 N·m
L1, L2, L3, T1/U, T2/V, T3/W, UDC+, UDC-: 30 N·m
9.8 N·m
Note: For frame R8: Install the side plates if removed.
Note: For frame R8: The power cable connectors can be detached. For the
instructions, see section R8 power cable connection if you detach the cable
connectors (page 109).
11. For frame R8: Install the EMC plates in reverse order. See step 4.
12. For frame R6 types bigger than -040A-x: Cut tabs in the shroud for the installed
cables.