Calculating the short-circuit current of the installation
Make sure that the short-circuit current of the installation is at least the value
given in the fuse table.
The short-circuit current of the installation can be calculated as follows:
I
k2-ph
=
2 ·
R
c
2
+ (Z
k
+ X
c
)
2
U
where
Short-circuit current in symmetrical two-phase short-circuit
I
k2-ph
Network line-to-line voltage (V)
U
Cable resistance (ohm)
R
c
Z
k
=
z
k
·
U
n
2
/
S
n
= transformer impedance (ohm)
Z
k
Transformer impedance (%)
z
k
Transformer rated voltage (V)
U
n
Nominal apparent power of the transformer (kVA)
S
n
Cable reactance (ohm)
X
c
Calculation example
Drive:
ACH580-31-145A-4
supply voltage = 410 V
Transformer:
rated power
S
n
= 600 kVA
rated secondary voltage (supply for drive supply)
U
n
= 430 V
transformer impedance z
k
= 7.2%
Supply cable:
length = 170 m
resistance/length = 0.398 ohm/km
reactance/length = 0.082 ohm/km.
Technical data 181