Loading...
Package weightFrame
size
lbkg
51.623.4R3
164.974.8R6
299.8
2)
136
1)
R8
1)
for types -105A-3, 145A-3, -101A-5, -124A-5: 121 kg
2)
for types -105A-3, 145A-3, -101A-5, -124A-5: 266.8 lb
Losses, cooling data and noise
The air flow direction is from bottom to top.
This table shows typical heat loss values, required air flow and noise at the nominal
ratings of the drive. The heat loss values can vary depending on voltage, cable
conditions, motor efficiency and power factor. To obtain more accurate values for
given conditions, use ABB DriveSize tool
(http://new.abb.com/drives/software-tools/drivesize).
IEC
FrameNoiseAir flowHeat dissipationACH580-
31-…
Main cir-
cuit and
control
boards
Control
circuit
maxim-
um
Control
circuit
minim-
um
Main cir-
cuit at
rated
I
1
at
I
2
dB(A)ft
3
/minm
3
/hWWWW
U
n
= 400 V
R357212361226364.119009A5-4
R357212361329364.129312A7-4
R357212361395364.1359018A-4
R357212361579364.1543026A-4
R671324550625364.1589033A-4
R671324550751364.1715039A-4
R671324550912364.1876046A-4
R6713245501088364.11052062A-4
R6713245501502364.11466073A-4
R6713245501904364.11868088A-4
R868
506/537
1)
860/913
1)
1877364.11841106A-4
R868
506/537
1)
860/913
1)
2963364.12927145A-4
R868
506/537
1)
860/913
1)
3168364.13132169A-4
R868
506/537
1)
860/913
1)
3990364.13954206A-4
U
n
= 480 V
190 Technical data