• The maximum number of conductors per terminal is 1.
Note: Only copper cables are allowed for drive types up to -039A-4.
Terminal and entry data for the control cables
■
IEC
Control cable entries, wire sizes and tightening torques (
T
) are given below.
Control cable entries and terminal sizesCable entriesFrame
DI, AI/O, AGND, RO, STO
terminals
+24V, DCOM, DGND, EXT.
24V terminals
Max cable
size
Holes
T
Wire size
T
Wire size
N·mmm
2
N·mmm
2
mmpcs
0.5…0.60.14…2.50.5…0.60.2…2.5174R3
0.5…0.60.14…2.50.5…0.60.14…2.5174R6
0.5…0.60.14…2.50.5…0.60.14…2.5174R8
■
UL
Control cable entries, wire sizes and tightening torques (
T
) are given below.
Control cable entries and terminal sizesCable entriesFrame
size
DI, AI/O, AGND, RO, STO
terminals
+24V, DCOM, DGND, EXT.
24V terminals
Max cable
size
Holes
T
Wire size
T
Wire size
lbf·ftAWGlbf·ftAWGinpcs
0.426…140.424…140.674R3
0.426…140.426…140.674R6
0.426…140.426…140.674R8
Typical power cables
The table below gives typical copper and aluminum cable types with concentric
copper shield for the drives with nominal current. For protective earth conductor
sizing, see Grounding requirements (page 72). For terminal and entry data for
power cables, see Terminal and entry data for the power cables (page 194).
UL (NEC)
3)
IEC
1)
Frame
size
ACH580-
31-…
Cu cable typeAl cable type
2)
Cu cable type
AWG/kcmilmm
2
mm
2
U
n
= 400 V
14-3×2.5R309A5-4
Technical data 195