EasyManua.ls Logo

ABB ACH580-31 - Ar Fuses DIN 43620 Blade Style; Gg Fuses DIN 43620 Blade Style

ABB ACH580-31
284 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
aR fuses DIN 43620 blade style
Ultra-rapid (aR) fuses blade style (one fuse per phase)Input cur-
rent
Min.
short-cir-
cuit cur-
rent
1)
ACH580-
31-…
Type
DIN 43620
Bussmann
type
Voltage
rating
I
2
tNominal
current
VA
2
sAAA
3-phase
U
n
= 400 V
000170M1561690130258.06509A5-4
000170M15616901302510.06512A7-4
000170M15636904604014.0120018A-4
000170M15636904604020.0120026A-4
000170M156569014506327.0170033A-4
000170M156569014506333.0170039A-4
000170M156669025508040.0280046A-4
000170M1567690465010051.0380062A-4
000170M1568690850012563.0500073A-4
000170M15696901600016076.0700088A-4
000170M15696901650016094700106A-4
000170M381769046500315128900145A-4
2170M5808690790004001541900169A-4
2170M58096901550004501882200206A-4
1)
Minimum short-circuit current of the electrical power system
gG fuses DIN 43620 blade style
gG fuses can be used for frame R3 if they operate rapidly enough (max. 0.1 seconds).
ABB recommends, however, aR fuses. gG fuses are not allowed for frames R6 and
R8.
gG fuses (one fuse per phase)Input cur-
rent
Min.
short-cir-
cuit cur-
rent
1)
ACH580-
31-…
IEC 60269
size
ABB typeVoltage
rating
I
2
tNominal
current
VA
2
sAAA
3-phase
U
n
= 400 V
000OFAF000H16500740168.012809A5-4
000OFAF000H165007401610.012812A7-4
000OFAF000H2550025002514.0200018A-4
000OFAF000H3250040003220.0256026A-4
1)
Minimum short-circuit current of the installation
180 Technical data

Table of Contents

Other manuals for ABB ACH580-31

Related product manuals