ABB moulded case circuit breaker (Tmax)FrameACH580-
31-…
kA
1)
Type
65XT2H 160 EKIP DIP LS/I IN 63R3026A-4
65XT2H 160 EKIP DIP LS/I IN 100R6033A-4
65XT2H 160 EKIP DIP LS/I IN 100R6039A-4
65XT2H 160 EKIP DIP LS/I IN 100R6046A-4
65XT2H 160 EKIP DIP LS/I IN 160R6062A-4
65XT2H 160 EKIP DIP LS/I IN 160R6073A-4
65XT2H 160 EKIP DIP LS/I IN 160R6088A-4
65XT4H 250 EKIP DIP LS/I In 250AR8106A-4
65XT4H 250 EKIP DIP LS/I In 250AR8145A-4
65XT4H 250 EKIP DIP LS/I In 250AR8169A-4
65XT4H 250 EKIP DIP LS/I In 250AR8206A-4
U
n
= 480 V
65XT2H 160 EKIP DIP LS/I IN 25R309A5-4
65XT2H 160 EKIP DIP LS/I IN 25R312A7-4
65XT2H 160 EKIP DIP LS/I IN 63R3018A-4
65XT2H 160 EKIP DIP LS/I IN 63R3026A-4
65XT2H 160 EKIP DIP LS/I IN 100R6033A-4
65XT2H 160 EKIP DIP LS/I IN 100R6039A-4
65XT2H 160 EKIP DIP LS/I IN 100R6046A-4
65XT2H 160 EKIP DIP LS/I IN 160R6062A-4
65XT2H 160 EKIP DIP LS/I IN 160R6073A-4
65XT2H 160 EKIP DIP LS/I IN 160R6088A-4
65XT4H 250 EKIP DIP LS/I In 250AR8106A-4
65XT4H 250 EKIP DIP LS/I In 250AR8145A-4
65XT4H 250 EKIP DIP LS/I In 250AR8169A-4
65XT4H 250 EKIP DIP LS/I In 250AR8206A-4
1)
Maximum allowed rated conditional short-circuit current (IEC 61800-5-1) of the electrical power network.
Circuit breakers (UL)
The drives are suitable for use on a circuit capable of delivering not more than
65 kA symmetrical amperes (RMS) at 480 V maximum when protected by circuit
breakers in the tables below.
Additional fuse protection is not required when using the circuit breakers herein.
Circuit breakers are not required to be in the same enclosure as the drive.
Notes below the table must be followed when using these breakers.
Technical data 185