WARNING!
Do not connect the +24 V AC cable to the control unit ground when the control
unit is powered using an external 24 V AC supply.
Start-up
Setting the parameters
1. Power up the drive.
2. If no warning is shown,
make sure that the values of both parameters 15.01 Extension module type
and 15.02 Detected extension module are CMOD-02.
If the warning A7AB Extension I/O configuration failure is shown,
make sure that the value of parameter 15.02 is CMOD-02.
set the parameter 15.01 value to CMOD-02.
You can now see the parameters of the extension module in parameter group
15 I/O extension module.
Diagnostics
Faults and warning messages
Warning A7AB Extension I/O configuration failure.
LEDs
The extension module has one diagnostic LED.
DescriptionColor
The extension module is powered up.Green
Technical data
Into option slot 2 on the drive control unitInstallation
IP20 / UL Type 1Degree of protection
See the drive technical data.Ambient conditions
CardboardPackage
Motor thermistor connection (60…61)
1.5 mm
2
Maximum wire size
DIN 44081 and DIN 44082Supported standards
3.6 kohm ±10%Triggering threshold
1.6 kohm ±10%Recovery threshold
5.0 VPTC terminal voltage
280 CMOD-02 multifunction extension module (external 24 V AC/DC and isolated
PTC interface)