WARNING!
Do not connect the +24 V AC cable to the control unit ground when the control
unit is powered using an external 24 V AC supply.
Start-up
■
Setting the parameters
1. Power up the drive.
2. If no warning is shown,
• make sure that the values of both parameters 15.01 Extension module type
and 15.02 Detected extension module are CMOD-02.
If the warning A7AB Extension I/O configuration failure is shown,
• make sure that the value of parameter 15.02 is CMOD-02.
• set the parameter 15.01 value to CMOD-02.
You can now see the parameters of the extension module in parameter group
15 I/O extension module.
Diagnostics
■
Faults and warning messages
Warning A7AB Extension I/O configuration failure.
■
LEDs
The extension module has one diagnostic LED.
DescriptionColor
The extension module is powered up.Green
Technical data
Into option slot 2 on the drive control unitInstallation
IP20 / UL Type 1Degree of protection
See the drive technical data.Ambient conditions
CardboardPackage
Motor thermistor connection (60…61)
1.5 mm
2
Maximum wire size
DIN 44081 and DIN 44082Supported standards
3.6 kohm ±10%Triggering threshold
1.6 kohm ±10%Recovery threshold
≤ 5.0 VPTC terminal voltage
280 CMOD-02 multifunction extension module (external 24 V AC/DC and isolated
PTC interface)