Max. 95%Max. 95%5 to 95%Relative humidity
No condensation allowed. Maximum allowed relative humidity is
60% in the presence of corrosive gases.
IEC 60721-3-2: 1997IEC 60721-3-1: 1997IEC 60721-3-3: 2002Contamination levels
(IEC 60721-3-x)
Class 2C2Class 1C2Class 3C2Chemical gases
Class 2S2Class 1S3 (packing
must support this,
otherwise 1S2)
Class 3S2. No conduct-
ive dust allowed.
Solid particles
--2Pollution degree
(IEC/EN 60664-1)
60 to 106 kPa70 to 106 kPa70 to 106 kPaAtmospheric pressure
0.6 to 1.05 atmo-
spheres
0.7 to 1.05 atmo-
spheres
0.7 to 1.05 atmo-
spheres
--10...150 HzVibration
Amplitude
±0.075 mm,
10...57.56 Hz
(IEC 60068-2:6)
Constant peak acceler-
ation 10 m/s² (1 gn),
57.56...150 Hz
R3: Displacement, 25 mm peak to peak, 14200
vibratory impacts
-Vibration (ISTA)
R6, R8 ISTA 3E): Random, overall
Grms level of 0.54
R3 (ISTA 1A): Drop, 6 faces, 3 edges and 1
corner, 460 mm (18.1 in)
Not allowedShock/Drop (ISTA)
R6, R8 (ISTA 3E): Shock, incline impact: 1.2
m/s (3.94 ft/s)
Shock, rotational edge drop: 230 mm (9.1 in)
1)
For neutral-grounded TN and TT systems and non-corner grounded IT systems.
2)
For corner-grounded TN, TT and IT systems.
Markings
These markings are attached to the drive:
CE mark
Product complies with the applicable European Union legislation. For fulfilling
the EMC requirements, see the additional information concerning the drive EMC
compliance (IEC/EN 61800-3).
BTL (BACnet Testing Laboratories) mark
Product has BACnet conformance certificate.
Technical data 205