Electromagnetic compatibility (EMC) - Part 3-12: Limits - Limits for
harmonic currents produced by equipment connected to public low-
voltage systems with input current > 16 A and < 75 A per phase.
IEC/EN 61000-3-
12:2011
Limits - Limitation of emission of harmonic currents in low-voltage
power supply systems for equipment with rated current greater
than 16 A
IEC 61000-3-4:1998
Adjustable speed electrical power drive systems. Part 3: EMC require-
ments and specific test methods
IEC/EN 61800-3:2004
+ A1:2012
Adjustable speed electrical power drive systems. Part 5-1: Safety
requirements electrical, thermal and energy
IEC/EN 61800-5-
1:2007
Adjustable speed electrical power drive systems Part 9-2: Eco-
design for power drive systems, motor starters, power electronics
and their driven applications Energy efficiency indicators for power
drive systems and motor starters
IEC 61800-9-2: 2017
Standard for Adjustable Speed Electrical Power Drive Systems - Part
5-1: Safety Requirements -Electrical, Thermal and Energy
UL 61800-5-1: First
edition 2012
Insulation coordination for equipment within low-voltage systems.
Part 1: Principles, requirements and tests.
IEC/EN 60664-1:2007
Enclosures for Electrical Equipment (1000 Volts Maximum)NEMA 250:2014
Industrial control equipmentCSA C22.2 No. 274-17
Ambient conditions
Environmental limits for the drive are given below. The drive is to be used in a
heated, indoor, controlled environment. All printed circuit boards are conformal
coated.
Transportation in the
package
Storage in the pack-
age
Operation installed
for stationary use
-- 0 to 4000 m (13123
ft) above sea
level
1)
0 to 2000 m (6561
ft) above sea
level
2)
Output derated above
1000 m (3281 ft), see
Altitude derat-
ing (page 174).
Installation site alti-
tude
-40 to +70 °C (-40 to
+158 °F)
-40 to +70 °C (-40 to
+158 °F)
-15 to +50 °C (5 to
122 °F).
Surrounding air tem-
perature
No frost allowed.
See Derat-
ings (page 172).
204 Technical data

Table of Contents

Other manuals for ABB ACH580-31