EasyManua.ls Logo

ABB ACH580-31 - DI5 as Frequency Input; DI6 as PTC Input; AI1 and AI2 as Pt100, Pt1000, Ni1000, KTY83 and KTY84 Sensor Inputs (X1)

ABB ACH580-31
284 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
An example of a two-wire sensor/transmitter supplied by the drive auxiliary voltage
output is shown below. Set the input signal to 4…20 mA, not 0…20 mA.
4…20 mA
+
-
P
I
...
AI2
AGND
+24V
DGND
An example of a three-wire sensor/transmitter supplied by the drive auxiliary
voltage output is shown below.The sensor is supplied through its current output
and the drive feeds the supply voltage (+24 V DC). Thus the output signal must be
4…20 mA, not 0…20 mA.
4…20 mA
+
-
P
I
...
AI2
AGND
+24V
DGND
OUT
DI5 as frequency input
For setting the parameters for the digital frequency input, see the firmware manual.
DI6 as PTC input
If DI6 is used as a PTC input, see firmware manual for how to set parameters
accordingly.
Note: If DI6 is used as a PTC input, the wiring and the PTC sensor need to be double
isolated. Otherwise the CMOD-02 I/O extension module must be used.
1
...
+24V
DI6
+t°+t°+t°+t°+t°
+t°
One to six PTC thermistors connected in series1
AI1 and AI2 as Pt100, Pt1000, Ni1000, KTY83 and KTY84 sensor inputs
(X1)
Sensors for motor temperature measurement can be connected between an analog
input and output. An example connection is shown below. Leave the other end of
Control unit 141