Parameter setting example for frequency output
This example shows how to make digital output DO1 of the extension module
indicate the motor speed 0…1500 rpm with a frequency range of 0…10000 Hz.
SettingParameter
Frequency output15.22 DO1 configuration
01.01 Motor speed used15.33 Freq out 1 source
015.34 Freq out 1 src min
1500.0015.35 Freq out 1 src max
1000 Hz15.36 Freq out 1 at src min
10000 Hz15.37 Freq out 1 at src max
■
Diagnostics
Faults and warning messages
Warning A7AB Extension I/O configuration failure.
LEDs
The extension module has one diagnostic LED.
DescriptionColor
The extension module is powered up.Green
Technical data
Into an option slot on the drive control unitInstallation
IP20 / UL Type 1Degree of protection
See the drive technical data.Ambient conditions
CardboardPackage
Reley outputs (50…52, 53…55)
1.5 mm
2
Maximum wire size
12 V / 10 mAMinimum contact rat-
ing
250 V AC / 30 V DC / 2 AMaximum contact
rating
1500 VAMaximum breaking
capacity
Transistor output (42…44)
1.5 mm
2
Maximum wire size
Transistor output PNPType
CMOD-01 multifunction extension module (external 24 V AC/DC and digital I/O) 273