Terminal and entry data for the power cables
IEC
Input, motor and DC cable entries, maximum wire sizes (per phase) and terminal
screw sizes and tightening torques are given below.
PE terminalL1, L2, L3, T1/U, T2/V, T3/W, UD+, UDC- terminalsCable entriesFrame
T
Wire
screw
Wire
size
T
Wire
screw
Max wire size
(solid/ stranded)
Min wire size
(solid/ stranded)
2)
Ø
1)
pcs
N·mM…
mm
2
N·mM…
mm
2
mm
2
mm
1.7M5251.7M416.00.5233R3
2.9M63515M870.06.0453R6
9.8M618530M1015025453R8
1)
Maximum cable diameter accepted. For the bottom plate hole diameters, see chapter Dimension
drawings (page 213).
2)
Minimum wire size does not necessarily have enough current capability for full load. Make sure the
installation complies with local laws and regulations.
Note: Only copper cables are allowed for drive types up to -039A-4.
Screwdrivers for the terminals of the main circuitFrame
Flat blade 0.6 x 3.5 mmR3
UL
Input, motor and DC cable entries, maximum wire sizes (per phase) and terminal
screw sizes and tightening torques are given below.
PE terminalL1, L2, L3, T1/U, T2/V, T3/W, UD+, UDC- terminalsCable entriesFrame
T
Wire
screw
Wire size
T
Wire
screw
Max wire size
(solid/ stranded)
Min wire size
(solid/ stran-
ded)
2)
Ø
1)
pcs
lbf·ftM…AWG/kcmillbf·ftM…AWGAWGin
1.2M541.3M46200.913R3
2.1M6211.0M82/0101.773R6
7.2M6350 MCM22.5M10300 MCM41.773R8
1)
Maximum cable diameter accepted. For the bottom plate hole diameters, see chapter Dimension
drawings (page 213).
2)
Minimum wire size does not necessarily have enough current capability for full load. Make sure the
installation complies with local laws and regulations.
Note:
The minimum specified wire size does not necessarily have sufficient current
carrying capacity at maximum load.
The terminals do not accept a conductor that is one size larger than the
maximum specified wire size.