Recommended annual actions by the user
DescriptionAction
Capacitor reforming for spare modules and spare capacitorsP
Tightness of terminalsI
Dustiness, corrosion or temperatureI
Heatsink cleaningP
Recommended maintenance actions by the user
Years from start-upComponent
21181512963
Cooling
Main cooling fan
RRMain cooling fans
Auxiliary cooling fan
RRAuxiliary cooling fan
RRSecond auxiliary cooling fan (IP55, UL Type 12)
Aging
RRControl panel battery (real-time clock)
Functional safety
I
See the maintenance in-
formation of the safety
function
Safety function test
20 yearsSafety component expiry (Mission time,
T
M
)
4FPS10000309652
Note:
Maintenance and component replacement intervals are based on the
assumption that the equipment is operated within the specified ratings and
ambient conditions. ABB recommends annual drive inspections to ensure the
highest reliability and optimum performance.
Long term operation near the specified maximum ratings or ambient conditions
may require shorter maintenance intervals for certain components. Consult
your local ABB Service representative for additional maintenance
recommendations.