88 Program features
When adaptive voltage limit is disabled in parameter 95.02:
Settings and diagnostics
Parameters 01.11 DC voltage (page 108), 30.30 Overvoltage control (page 203),
30.31 Undervoltage control (page 203), 95.01 Supply voltage (page 274) and 95.02
Adaptive voltage limits (page 275).
Events: -
DC voltage level [V] 95.01 Supply Voltage
See 95.01 Supply voltage.
Supply voltage
range [V] 180…415
Supply voltage
range [V] 440…480
Automatic /
Not selected
if 95.03
< 456AC
if 95.03
> 456AC
Overvoltage fault limit 842 842 842
Overvoltage control limit 779 779 779
Overvoltage warning limit 745 745 745
Undervoltage warning limit
0.85×1.35×180 = 436
0.85×1.35×440 =
504
0.85×1.35×180
= 436
0.85×1.35×440
= 505
Undervoltage control limit 0.78×1.35×180 =400
0.78×1.35×440 =
463
0.78×1.35×180
= 400
0.78×1.35×440
= 463
Charging relay closing limit
0.78×1.35×180 = 400
0.78×1.35×440 =
463
0.78×1.41×par
95.03 value
1)
Charging relay opening
limit
0.73×1.41×par 95.03
value
1)
0.78×1.41 ×par
95.03 value
1)
0.73×1.41×par
95.03 value
1)
DC voltage at upper bound
of supply voltage range
(U
DCmax
)
560 648
DC voltage at lower bound
of supply voltage range
(U
DCmin
)
513 594
Charging
activation/standby limit
0.73×1.41×par 95.03
value
1)
0.73×1.41×par
95.03 value
1)
0.73×1.41×par
95.03 value
1)
Undervoltage fault limit
3)
0.45×1.41×par 95.03
value
1)
0.45×1.41×par
95.03 value
1)
0.45×1.41×par
95.03 value
1)
1)
If parameter 95.01 Supply voltage is set to Automatic / not selected and 95.02 Adaptive voltage limits
is set to Enable, the value of parameter 95.03 Estimated AC supply voltage is used,
2)
otherwise the
lower limit of the range selected with parameter 95.01 Supply voltage is used.
3)
The drive trips on the undervoltage fault when parameter 21.18 (Auto restart time) elapses or the value
of parameter 21.18 is 0. In that case the standby limit is used as the undervoltage trip level. The
undervoltage fault occurs only if the drive is modulating when the DC voltage drops below the
undervoltage trip level.
ACS180 FW.book Page 88 Tuesday, March 9, 2021 2:25 PM