Program features 49
If necessary, the default parameter values can be restored by parameter 96.06
Parameter restore.
Settings and diagnostics
Parameters: 96.06 Parameter restore...96.07 Parameter save manually.
Events: -
Control interfaces
Programmable analog inputs
There are two programmable analog inputs. Each of the inputs can be independently
set as a voltage (0/2…10 V) or current (0/4…20 mA) input by parameter. Each input
can be filtered, inverted and scaled. AI1 can be configured as DI5 by parameter.
Settings and diagnostics
Parameter group 12 Standard AI and 11.21 DI5 configuration.
Events: -
Programmable analog outputs
There is one analog output voltage (0/2…10 V) or current (0/4…20 mA) output (can
be set by parameter). The output can be filtered, inverted and scaled.
Settings and diagnostics
Parameter group 13 Standard AO.
Events: -
Programmable digital inputs and outputs
There are four digital inputs, and one digital outputs. In addition, the analog input AI1
can be configured as digital input DI5 by a parameter.
Digital inputs DI3 and DI4 can be used as frequency input.
Settings and diagnostics
Parameter groups 10 Standard DI, RO and 11 Standard DIO, FI, FO.
Events: -
Programmable relay outputs
There is one relay output. The signal indicated by the output can be selected by a
parameter.
ACS180 FW.book Page 49 Tuesday, March 9, 2021 2:25 PM