276 Parameters
95.26 Motor disconnect
detection
Enables the use of the motor disconnect switch, or selects
the source for the enable signal. When enabled, the drive
does not trip to a fault when it detects the disconnection
but remains operational and returns to normal operation
after a reconnection.
When this parameter is enabled, the drive will go through
the following sequence:
1. Motor is disconnected: Drive detects the disconnection
and indicates it with warning A784. The drive remains
in operation and waits for motor reconnection.
2. Motor is reconnected: Drive detects the reconnection,
removes the warning and returns to normal operation.
The last active reference before the disconnection is in
use.
Note: This feature is only available in scalar mode. This
parameter does not affect vector mode behavior.
Disable
0Disable. 1 = 1
1 Enable. 1 = 1
95.200 Cooling fan mode Change the cooling fan control mode Auto
Auto Cooling fan is controlled automatically 0
Always on Cooling fan is always running 1
96
96 System
Language selection; access levels; macro selection;
parameter save and restore; control unit reboot; user
parameter sets; unit selection; parameter checksum
calculation; user lock.
96.01 Language Selects the language of the parameter interface and other
displayed information when viewed on the control panel.
Notes:
• Not all languages listed below are necessarily
supported.
• This parameter does not affect the languages visible in
the Drive composer PC tool. (Those are specified
under View – Settings – Drive default language.)
Not selected
Not selected Select a language. 0
English English. 1033
Deutsch German. 1031
Italiano Italian. 1040
Español Spanish. 3082
Portugues Portuguese. 2070
Nederlands Dutch. 1043
Français French. 1036
Suomi Finnish. 1035
Svenska Swedish. 1053
Russki Russian. 1049
Polski Polish. 1045
Türkçe Turkish. 1055
Chinese (Simplified,
PRC)
Simplified Chinese. 2052