274 Parameters
71.23 Internal setpoint 3 See parameter 40.23 Set 1 internal setpoint 3. 0.00 PID
customer
units
71.26 Setpoint min See parameter 40.26 Set 1 setpoint min.0.00
71.27 Setpoint max See parameter 40.27 Set 1 setpoint max. 200000.00
71.31 Deviation inversion See parameter 40.31 Set 1 deviation inversion. Not inverted
(Ref - Fbk)
71.32 Gain See parameter 40.32 Set 1 gain.1.00
71.33 Integration time See parameter 40.33 Set 1 integration time.60.0 s
71.34 Derivation time See parameter 40.34 Set 1 derivation time. 0.000 s
71.35 Derivation filter time See parameter 40.35 Set 1 derivation filter time. 0.0 s
71.36 Output min See parameter 40.36 Set 1 output min. -200000.00
71.37 Output max See parameter 40.37 Set 1 output max. 200000.00
71.38 Output freeze enable See parameter 40.38 Set 1 output freeze enable. Not selected
71.39 Deadband range The control program compares the absolute value of
parameter 71.04 Deviation act value to the deadband
range defined by this parameter. If the absolute value is
within the deadband range for the time period defined by
parameter 71.40 Deadband delay, PID's deadband mode
is activated and 71.06 PID status word bit 9 Deadband
active is set. Then PID's output is frozen and 71.06 PID
status word bit 2 Output frozen is set.
If the absolute value is equal or greater than the
deadband range, PID's deadband mode is deactivated.
0.0
0.0…200000.0 Range 1 = 1
71.40 Deadband delay Defines the deadband delay for the deadband function.
See parameter 71.39 Deadband range.
0.0 s
0.0…3600.0 s Delay 1 = 1 s
71.58 Increase prevention See parameter 40.58 Set 1 increase prevention. No
71.59 Decrease prevention See parameter 40.59 Set 1 decrease prevention. No
71.62 Internal setpoint actual See parameter 40.62 PID internal setpoint actual. -
71.79 External PID units See parameter 40.79 Set 1 units. 4
76
95 HW configuration
Various hardware-related settings.
95.01 Supply voltage Selects the supply voltage range. This parameter is used
by the drive to determine the nominal voltage of the supply
network. The parameter also affects the current ratings
and the DC voltage control functions (trip and brake
chopper activation limits) of the drive.
WARNING! An incorrect setting may cause the
motor to rush uncontrollably, or the brake chopper
or resistor to overload.
Note: The selections shown depend on the hardware of
the drive. If only one voltage range is valid for the drive in
question, it is selected by default.
Automatic /
not selected
Automatic / not
selected
No voltage range selected. The drive will not start
modulating before a range is selected, unless parameter
95.02 Adaptive voltage limits is set to Enable, in which
case the drive estimates the supply voltage itself.
0
No. Name/Value Description Default
FbEq 16
ACS180 FW.book Page 274 Tuesday, March 9, 2021 2:25 PM