EasyManua.ls Logo

ABB ACS180 - Page 94

ABB ACS180
392 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
94 Program features
Overspeed protection (parameter 31.30)
The user can set overspeed (and overfrequency) limits by specifying a margin that is
added to the currently-used maximum and minimum speed (or frequency) limits.
Local control loss detection (parameter 49.05)
The parameter selects how the drive reacts to a control panel or PC tool
communication break.
AI supervision (parameters 12.0312.04)
The parameters select how the drive reacts when an analog input signal moves out of
the minimum and/or maximum limits specified for the input.
Ramp stop supervision (parameters 31.32, 31.33, 31.37 and 31.38)
The control program has a supervision function for both the normal and emergency
stop ramps. The user can either define a maximum time for stopping, or a maximum
deviation from the expected deceleration rate. If the drive fails to stop in the expected
manner, a fault is generated and the drive coasts to a stop.
Custom motor current fault limit (parameter 31.30)
The control program sets a motor current limit based on drive hardware. In most
cases, the default value is appropriate. However, a lower limit can be manually set by
the user, for example, to protect a permanent magnet motor from demagnetization.
ACS180 FW.book Page 94 Tuesday, March 9, 2021 2:25 PM