8405 SEQ ST
FORCE
Forces the Sequence programming to a selected state.
Note: State is changed only when Sequence programming
is paused by parameter 8403 SEQ PROG PAUSE and this
parameter is set to the selected state.
STATE 1
STATE 1 State is forced to state 1. 1
STATE 2 State is forced to state 2. 2
STATE 3 State is forced to state 3. 3
STATE 4 State is forced to state 4. 4
STATE 5 State is forced to state 5. 5
STATE 6 State is forced to state 6. 6
STATE 7 State is forced to state 7. 7
STATE 8 State is forced to state 8. 8
8406 SEQ LOGIC
VAL 1
Defines the source for the logic value 1. Logic value 1 is
compared to logic value 2 as defined by parameter 8407
SEQ LOGIC OPER 1.
Logic operation values are used in state transitions. See
parameter 8425 ST1 TRIG TO ST 2 / 8426 ST1 TRIG TO
ST N selection LOGIC VAL.
NOT SEL
DI1(INV) Logic value 1 through inverted digital input DI1 -1
DI2(INV) See selection DI1(INV).-2
DI3(INV) See selection DI1(INV).-3
DI4(INV) See selection DI1(INV).-4
DI5(INV) See selection DI1(INV).-5
NOT SEL No logic value 0
DI1 Logic value 1 through digital input DI1 1
DI2 See selection DI1.2
DI3 See selection DI1.3
DI4 See selection DI1.4
DI5 See selection DI1.5
SUPRV1
OVER
Logic value according to supervision parameters
3201…3203. See parameter group 32 SUPERVISION.
6
SUPRV2
OVER
Logic value according to supervision parameters
3204…3206. See parameter group 32 SUPERVISION.
7
SUPRV3
OVER
Logic value according to supervision parameters
3207…3209. See parameter group 32 SUPERVISION.
8
SUPRV1
UNDER
See selection SUPRV1 OVER.9
SUPRV2
UNDER
See selection
SUPRV2 OVER.10
All parameters