EasyManua.ls Logo

ABB ACS380 Series - Page 403

ABB ACS380 Series
462 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Fieldbus control through the embedded fieldbus interface (EFB) 403
CiA 402 profile state machine
CW: Control word
SW: Status word
From any state
START
FAULT REACTION
ACTIVE
SW: xxxxxxxxx0xx1111
NOT READY TO
SWITCH ON
SW: xxxxxxxxx0xx0000
FAULT
SW: xxxxxxxxx0xx1000
SWITCH-ON
DISABLED
SW: xxxxxxxxx1xx0000
READY TO SWITCH ON
SW: xxxxxxxxx01x0001
SWITCHED ON
SW: xxxxxxxxx01x0011
OPERATION
ENABLED
SW: xxxxxxxxx01x0111
QUICK STOP ACTIVE
SW: xxxxxxxxx0xx0111
(9)
(11)
CW: xxxxxxxxxxxxxx0x
CW: xxxxxxxxxxxxx01x
(8)
(12)
(4)
(5)
CW: xxxxxxxxxxxx1111
CW: xxxxxxxxxxxxx110
CW: xxxxxxxxxxxx0111
CW: xxxxxxxxxxxxx110
CW: xxxxxxxxxxxxx111
(3)
(6)
CW: xxxxxxxxxxxxxx0x
Quick stop
completed or
(10)
CW: xxxxxxxxxxxxx01x
or
CW: xxxxxxxxxxxxxx0x
(2)
(7)
(15)
(1)
CW: xxxxxxxxxxxxx110
CW: xxxxxxxxxxxxx01x
or
CW: xxxxxxxxxxxxxx0x
CW: xxxxxxxx1xxxxxxx
Initialized
successfully
Fault reaction
completed
Power-on,
self-initialization
State transition
(0)

Table of Contents