94 Program features
Programmable protection functions
External events (parameters 31.0131.10)
Five different event signals from the process can be connected to selectable inputs to
generate trips and warnings for the driven equipment. When the signal is lost, an
external event (fault, warning, or a mere log entry) is generated.
Motor phase loss detection (parameter 31.19)
The parameter selects how the drive reacts whenever a motor phase loss is detected.
Earth (Ground) fault detection (parameter 31.20)
Note that
an earth fault in the supply cable does not activate the protection
in a grounded supply, the protection activates within 2 milliseconds
in an ungrounded supply, the supply capacitance must be 1 microfarad or more
the capacitive currents caused by shielded motor cables up to 300 meters will not
activate the protection
the protection is deactivated when the drive is stopped.
Supply phase loss detection (parameter 31.21)
The parameter selects how the drive reacts whenever a supply phase loss is
detected.
Safe torque off detection (parameter 31.22)
The drive monitors the status of the Safe torque off input, and this parameter selects
which indications are given when the signals are lost. (The parameter does not affect
the operation of the Safe torque off function itself). For more information on the Safe
torque off function, see the hardware manual of the drive.
Swapped supply and motor cabling (parameter 31.23)
The drive can detect if the supply and motor cables have accidentally been swapped
(for example, if the supply is connected to the motor connection of the drive). The
parameter selects if a fault is generated or not.
Stall protection (parameters 31.2431.28)
The drive protects the motor in a stall situation. It is possible to adjust the supervision
limits (current, frequency and time) and choose how the drive reacts to a motor stall
condition.
Overspeed protection (parameter 31.30)
The user can set overspeed (and overfrequency) limits by specifying a margin that is
added to the currently-used maximum and minimum speed (or frequency) limits.